Answers are grounded in this paper and cite their sources.
This article describes the use of FLUENT software to simulate the heat transfer performance of U-tube heat exchangers in the ground source heap pump using the backfill materials of shape-stabilized phase change materials and crushed stone concrete. In this study, the shape-stabilized phase change material is a mixture of decanoic acid and lauric acid with the following mass concentration compositions: decanoic acid = 60%, silica = 10%, and expanded graphite = 6%. The mixture of shape-stabilized phase change material has a coefficient of thermal conductivity of 1.528 W/(m·K) and a latent heat of 109.2 kJ/kg. From the results of a 12-h simulation of the heat transfer dynamics, the heat exchange for a unit borehole depth of backfilling with shape-stabilized phase change material is 1.223 times the heat exchange for a unit borehole depth of backfilling with crushed stone concrete. In addition, the thermal influence radius of the backfill materials of shape-stabilized phase change material is 0.9 times of that of crushed stone concrete. As a result, under the same area of the buried pipes region, the shape-stabilized phase change material backfill can achieve a heat exchange 1.359 times that of crushed stone concrete backfill. Meanwhile, using shape-stabilized phase change material could contain the sustaining decline in coefficient of performance of heat pump at refrigerate condition to a certain extent and the appropriate physical parameters of phase change materials are also crucial.
No takes yet. Share an insight, caveat, or question.
Li et al. (2017) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: