Answers are grounded in this paper and cite their sources.
Grid-connected converters require advanced controllers in order to achieve high performance and meet country-specific anti-islanding standards. This paper presents a novel, high performance islanding search sequence (ISS) technique applied to four islanding detection methods. The salient aspects of the proposed determination technique reside in its fault-tolerant safety redundancy with rapid unintentional islanding detection integrated within: active-reactive power control, maximum power point tracking (MPPT) algorithm, and phase-locked loop routine. The islanding detection search sequence method is successfully implemented within a voltage-oriented inverter controller using a synchronously rotating reference frame. The ISS structure is designed with an adaptive strategy to achieve system stability and minimum impact on power quality, and is applicable to grid-connected distributed power generators. The adaptive search sequence results in fast detection, robust operation, and most importantly, a reduced reactive and active power injection. The proposed control structure and detection methods performance are demonstrated through experimental results of a three-phase, 20-kVA three-level neutral-point-clamped transformerless inverter. The evaluation results on the grid-interactive inverter include the islanding detection method integrated in the MPPT used in renewable energy harvesting applications.
No takes yet. Share an insight, caveat, or question.
Serban et al. (2014) studied this question.