Answers are grounded in this paper and cite their sources.
This letter presents a novel robust prony method for power system oscillatory modes monitoring that is immune to synchrophasor measurement noise and outliers. The conventional least squares for polynomial coefficients estimation is reformulated as a structural weighted total least square (WTLS) estimation problem to mitigate the impact of measurement noise. To enhance the robustness of WTLS for handling gross measurement errors, i.e., outliers, Huber type M-estimator is advocated and solved by means of an iteratively reweighted regression algorithm. Numerical results on the simplified realistic WECC 179-bus system demonstrate the effectiveness and robustness of the proposed method.
No takes yet. Share an insight, caveat, or question.
Zhao et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: