A static water pipe in a cold snap is a clock: the water cools to 0 °C, ice begins to form, and the bore eventually freezes across. This paper computes that clock for three stated pipe sizes in a stated cold snap of −18.0 °C, with water starting at 10.0 °C. Bare pipes form their first ice quickly — after 0.19 hours for a 13 mm bore, 0.35 hours for a 25 mm bore, and 0.68 hours for a 50 mm bore — and freeze fully across in 1.55, 3.22, and 6.64 hours respectively. Against a stated design night of 12 hours, the closed-cell foam insulation (conductivity 0.040 W/(m·K)) required to keep the bore from freezing across is 4.0 mm for the 50 mm pipe and 22.3 mm for the 25 mm pipe, but 367.2 mm for the 13 mm pipe — a thickness no one will fit, which means small-bore pipes cannot be protected through such a night by passive insulation alone at any practical thickness. The alternative, a continuous trickle through a stated 10 m exposed run, costs 119.3 litres per night for the bare 13 mm pipe and 51.6 litres per night with 13 mm of foam, against 208.8 litres per night for the bare 25 mm pipe. A token drip of 0.05 litres per minute delivers 34.9 W of heat over the run, less than the 115.6 W the bare 13 mm run loses, so a dripping tap at that rate does not protect the pipe in this cold snap.