The article presents experimental data on the application of power harmonic filters (PHFs) in a 10 kV network of an industrial enterprise. Based on real-world data, the voltage rise on the 10 kV busbars and the reduction in active power losses were calculated for various switching configurations of the 3rd, 5th, 7th, and 11th harmonic filters. An emergency operating mode is analyzed in which all workshop substations are powered by a single step-down transformer, leading to its overload. Calculations prove that switching on all PHFs ensures a 25.4% transformer unloading and increases the power factor to 0.98. Recommendations for the further modernization of the enterprise's power supply system are provided.