With the continuous growth of electric power load, transformers act as the core equipment in power grids, and control of their operating temperature control is directly related to insulation service life and system safety. Parameter tuning of traditional PID control relies on engineering, and it is difficult to achieve systematic balance among energy efficiency, response speed and stability. This paper proposes a parameter optimization method for an intelligent transformer refrigeration system based on Latin Hypercube Sampling (LHS), Kriging surrogate model and Multi-Objective Particle-Swarm Optimization (MOPSO). The results show that the optimal parameter combination is Kp = 679.60, Ki = 0.12 and Kd = 39.89. Compared with parameters tuned by traditional empirical methods, the optimized COP increases by approximately 15%, and the overshoot decreases by approximately 96.3%. These results verify the effectiveness of the proposed method in balancing energy efficiency and dynamic performance.
No takes yet. Share an insight, caveat, or question.
Tie et al. (2026) studied this question.