Cold thermal energy storage applications at very low temperatures require a refrigeration unit that can provide cooling efficiently while limiting the environmental effect of the working fluids. This study evaluates the refrigeration subsystem of a cascade vapor compression system using propane (R290) in the high temperature cycle and ethane (R170) in the low temperature cycle. The analysis is performed under steady state conditions using energy, exergy, and advanced exergy methods. The base case uses a 5 kW cooling load and an evaporation temperature of − 80 °C. The real operating case gives a coefficient of performance (COP) of 0.6035, total power input of 8.285 kW, and total exergy destruction of 6.671 kW. The compressors account for 2.350 kW, or 35.2% of the total exergy destruction, followed by the cascade heat exchanger with 1.600 kW, or 24%. The unavoidable and ideal cases give COP values of 1.044 and 1.71, respectively. The selected refrigerants have zero ozone depletion potential and very low global warming potential. The present model evaluates the refrigeration cycle that can be coupled with a cold thermal energy storage unit; transient charging, discharging, storage sizing, and storage material behavior are outside the scope of this work. The results therefore identify improvement priorities for the refrigeration subsystem rather than the dynamic performance of a complete storage system.