Surface charging on insulator in DC-GIS is influenced by transient voltages like lightning impulse (LI) and polarity reversal (PR), which threatens the safe operation of the equipment. In this paper, a contour optimization method considering the influence of surface charging is proposed for insulator used in DC-GIS of ±320 kV. The insulation reliability under steady DC voltage is promoted, and the property to withstand the transient voltages is guaranteed as well. The normal and tangential components of electric field under steady DC voltage are simultaneously minimized, and the constraints on electric field under the transient voltages are incorporated. The results show that, under the steady DC voltage, the maximal value of normal electric field is reduced by 5.8%, and the tangential field is simultaneously reduced by 7.0% on the insulator with the optimal contour after optimization. The maximal values of electric fields under the LI and PR voltages are 8.82 and 3.49 kV/mm, respectively, meeting the insulation requirements. It is suggested that, the proposed method incorporating the property withstanding the LI and PR voltages yields a more reliable performance of the optimized insulator in DC-GIS.