This study proposes a topology analysis-based adaptive adjustment strategy for fault action zones in distribution networks incorporating distributed energy resources and reconfiguration switches. A weighted topological model is constructed by considering line impedance, load power, and distributed generation output, and complex-network metrics are used to quantify node and line importance. The strategy includes topology feature extraction, fault-zone sensitivity calculation, adaptive decision-making, and online updating mechanisms. Simulations on the IEEE 33-node system, IEEE 123-node system, and a selected real 10 kV feeder show that the proposed TAAS achieves a mean Zone Identification Accuracy of 97.3% ± 0.7%, a mean maloperation rate of 2.1% ± 0.2%, and a mean adjustment time of 14.8 ± 0.9 ms over 30 Monte Carlo repetitions. These results indicate improved performance relative to the tested FOC, IDZ, and DGNN baselines under the specified reconfiguration, DER-output fluctuation, noise, and missing-data conditions. Not applicable.