Dynamic operating envelopes give customers export or import limits; every combination of powers within them must respect network limits. In unbalanced networks the worst combination is not obvious; existing methods check selected scenarios or linearized models. This paper certifies an envelope on the nonlinear unbalanced power-flow model: for a given network and source voltage, with reactive powers fixed or in intervals, it proves that the power flow has a locally unique solution at every point of the box and bounds every voltage and branch current. It combines complex Taylor models with a Newton–Krawczyk test. On the IEEE European low-voltage feeder, a certificate takes 2.1–2.3 s and is within 0.01–0.83 V of the worst case found. At fixed loads, the all-at-limit check accepts envelopes exceeding the 253 V limit by up to 11.1 V; phase-wise scenarios are safe there up to the certificate's resolution, but must be redesigned when customers import, loads vary or three-phase customers are present. On a real four-wire network (313 customers), where unbalanced exports cause undervoltage through the neutral, the all-at-limit check accepts 1.9 times the certified limits. A certificate-guided sequential linear program designs envelopes, and the certificate repairs learned or scenario-optimized ones. This work has been submitted to the IEEE for possible publication. Copyright may be transferred without notice, after which this version may no longer be accessible.