Answers are grounded in this paper and cite their sources.
Gravity-fed water supply lines dissipate surplus head at break pressure tanks (BPTs), which, unlike pressure reducing valves, have not been appraised as a distinct micro-hydropower siting class. We develop a transferable framework—flow-duration scenarios, least-cost routing of grid connections weighted by 26 transmission experts, a vendor-quoted life-cycle cash flow appraisal valued with measured bills, and a water-quality risk assessment—and apply it to the Edremit line (Türkiye), where five BPTs offer 798 kW and 5.83 GWh in a typical year. The routes deviate only 7.4% from straight lines, whatever the weighting method. As the receiving pumping station consumes only 2.1–2.6 GWh/yr, about half of the output displaces purchases at 7.0 c€/kWh and the rest earns 3.7 c€/kWh; three stations remain viable at a 7% discount rate (internal rate of return 11.4–14.7%), and a fourth only with wider netting. Feasibility is set by the grid connection per kilowatt, not by the turbine: BPT-1, with 15.91 km of line for 35 kW, never recovers its capital. Applied to 84 municipal sites (25.5 MW), this break-even rule separates economically developable from technical potential. Water quality is protected by design: the retrofit adds no pressure boundary, storage or residence time.