Answers are grounded in this paper and cite their sources.
The growing use of nonlinear loads in industrial and residential applications degrades power quality through harmonic distortion and increased reactive power demand. Shunt active power filters (SAPFs) mitigate these disturbances at the point of common coupling (PCC). This paper proposes a modified packed E-cell nine-level inverter (MPEC9) for a single-phase SAPF. A Synergetic Model Predictive Decoupled Powers Control (DPC-SMPC) strategy combines synergetic control theory with model predictive control to regulate grid-side active and reactive powers while maintaining balanced DC-bus capacitor voltages. In this algorithm, the defined macro-variable is predicted to determine the optimal voltage vector associated with the active and reactive power references in a single evaluation. Subsequently, the capacitor voltages are predicted for all admissible switching states and incorporated into the cost function alongside the optimal voltage vector. The proposed DPC-SMPC achieves the control objectives with reduced computational burden. The proposed inverter and control strategy are evaluated through processor-in-the-loop (PIL) co-simulation. Comparative results against the DPC-MPC strategy demonstrate improved performance across the evaluated criteria and lower computational requirements, supporting the effectiveness of the proposed approach for power quality improvement and coordinated power regulation in the investigated single-phase SAPF system under evaluation.
No takes yet. Share an insight, caveat, or question.
Laib et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: