This study investigates how internal and external swirls affect the immediate near-field fine-droplet evolution of novel Swirl Burst (SB) twin-fluid injectors. Efficient fire suppression depends strongly on atomization. Unlike conventional jet-breaking injection, SB atomizers generate fine sprays immediately through primary atomization by bubble-bursting and secondary breakup by shear-layer instabilities. In this work, internal and/or external swirls are introduced to enhance primary atomization (SBP), secondary atomization (SBS), or both combined (SBC and reverse-swirl SBCR). Traditional laser-based optical diagnostics struggle to simultaneously resolve fine droplets and achieve high temporal resolution when investigating spray dynamics. Therefore, high-speed X-ray imaging at 3 µm/pixel and 5 MHz was used to capture previously incompletely resolved fine droplets (~6–30 µm) for the fine SB atomization and quantify droplet size and mass distributions at an air-to-liquid mass ratio (ALR) of 1.75. Results showed that all SB injectors produced fine droplets, with more than 90% below 18 µm at 9 mm downstream. SBCR provided the most uniform droplet distribution with improved stability, while SBP and SBS produced the widest and narrowest spray respectively. Furthermore, SBP has the highest estimated atomization efficiency, followed by SBC, SBCR, and SBS for droplets ranging from ~6–30 μm, confirming their potential for fire suppression and clean energy applications.
No takes yet. Share an insight, caveat, or question.
Ahmed et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: