Increasing renewable penetration strengthens the need for fast active-power support from converter-based power plants. Within a hybrid plant, grid-following (GFL) and grid-forming (GFM) resources have different response dynamics and power margins. This paper proposes a plant-level supplementary active-power coordination strategy that combines complementary-filter allocation (CFA) with residual-headroom correction. A channel with zero steady-state gain generates a transient request, and a complementary filter pair routes its faster component to GFM and its slower component to GFL. The correction scales positive GFM commands using the power margin remaining after baseline frequency support. PowerFactory comparisons separate allocation at common settings from independently tuned performance. For a 1.2 MW load increase with common settings and output limits disabled, CFA reduces the maximum frequency deficit by 19.9% relative to baseline droop and the total GFM peak power by 8.5% relative to GFM-only support, with greater GFL participation. In the averaged converter network, selected CFA lowers the measured 100 ms rate of change of frequency (RoCoF) by 26.6% relative to tuned fixed-ratio allocation (FRA), while FRA gives the higher minimum frequency. Separate correction tests show shorter clipping and smaller internal-angle excursions when the correction is active. The results identify how the strategy coordinates transient converter demand and frequency support under the tested resource constraints.