Thermal imaging identified an outdoor AC condenser as a low-grade waste heat source, with a measured local temperature difference of approximately 26 °C. A removable finned-tube HX was designed to recover condenser exhaust heat for service-water preheating without modifying the refrigerant circuit. Under moderate assumptions, the proposed system recovered 2.61 kW, equivalent to 15.77 kWh day⁻¹ and a theoretical electricity offset of approximately $5.17 day⁻¹ per condenser. The design is most suitable for sites where cooling operation overlaps with nearby hot-water demand.