Answers are grounded in this paper and cite their sources.
A resilient adaptive virtual synchronous generator (VSG) control framework is developed and evaluated for a 50-kW photovoltaic (PV)–battery islanded microgrid exposed to significant load changes and renewable-generation variability. The study employs 15-second dynamic simulations to compare conventional droop control with adaptive VSG control, assessing AC voltage, frequency, rate of change of frequency (RoCoF), battery power, state of charge (SOC), DC-link voltage, efficiency, power factor, current, and a modeled voltage-THD indicator. Results indicate that adaptive VSG reduces the visible peak frequency excursion and RoCoF compared to conventional droop control. However, the current tuning also yields substantially larger AC-voltage excursions and a more pronounced battery discharge response. These findings show that resilience assessment requires considering coordinated frequency, voltage, DC-link, and battery constraints, not frequency performance alone. Accordingly, a multi-objective resilience framework is formulated that adapts virtual inertia, damping, voltage-support gains, and battery support based on renewable/load disturbance severity and battery operating state. This approach establishes a dynamic baseline and a reproducible resilience-assessment framework that can be extended to additional external disturbances in future research.
No takes yet. Share an insight, caveat, or question.
Adeyinka et al. (2026) studied this question.
Synapse has enriched 8 closely related papers on similar clinical questions. Consider them for comparative context: