Large electronic loads can inject active-power oscillations into the grid, while grid-voltage disturbances may trigger load disconnection or transfer to backup supplies. This paper investigates how parallel grid-forming (GFM) energy storage modifies both disturbance paths using a unified small-signal network model of an integrated data-center system. Complementary electromagnetic-transient (EMT) frequency scans measure active-power sharing and identify coupled terminal admittance. Results demonstrate frequency-dependent power buffering and lower point-of-common-coupling (PCC) voltage sensitivity, with slight active-power amplification at low frequencies. A Nyquist-based assessment of measured and interpolated loop-eigenvalue responses shows greater measured separation from the critical point with GFM. A reduced analytical model then relates power sharing to network coupling, inertia, damping and droop, while its eigenvalues quantify modal stability and damping. Subsequent comparisons with EMT simulations give magnitude and complex-response errors below 5% across the evaluated baseline frequency scan and reproduce principal controller-tuning trends. The conclusions show that parallel GFM storage can buffer power fluctuations locally and reduce PCC voltage sensitivity, while controller tuning introduces trade-offs between power buffering and modal damping. The framework supports coordinated assessment of disturbance propagation and controller behavior under the studied small-signal conditions.