Confined pool boiling is increasingly relevant for compact high-heat-flux cooling systems, where the boiling surface and opposing confinement plate can strongly influence vapor removal and liquid replenishment. This study investigates the coupled effects of gap height and wettability of both opposing surfaces on pool boiling performance of distilled water at atmospheric pressure. Gold-coated copper boiling surfaces (14 mm diameter), comprising reference (REF), laser-textured superhydrophilic (SHPI), and superhydrophobic (SHPO) variants, were combined with 24-mm-diameter confinement plates of different wettability. The gap height varied from 0.1λ to 20λ, where λ = 2.5 mm is the capillary length of water. Under weak confinement (≥5λ), the upper plate had limited influence and boiling performance was governed predominantly by the boiling surface. Below 2.5λ, the wettability of both interfaces became increasingly important. The strongest deterioration occurred with the SHPI confinement plate above the reference boiling surface, whereas laser-textured boiling surfaces substantially improved performance. Relative to REF–REF at the same gap height, SHPI–SHPI increased CHF by up to 120% at 0.5λ and HTC at CHF by 708% at 0.1λ. SHPO–SHPI (confinement plate–boiling surface) provided the highest overall heat-transfer performance, increasing CHF by up to 113% at 0.5λ and HTC at CHF by 1257% at 0.1λ relative to REF–REF. Reversing the positions of SHPI and SHPO produced markedly different CHF under severe confinement, demonstrating that confined-boiling performance depends on both wettability pairing and spatial arrangement.
No takes yet. Share an insight, caveat, or question.
Hadžić et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: