Answers are grounded in this paper and cite their sources.
Previous V-rib studies have not systematically resolved how reversal of the V-opening direction across 90° interacts with rib height and Reynolds number in an aligned double-sided equal-branch configuration. To address this gap, three-dimensional conjugate heat transfer simulations were conducted for 225 microchannel configurations with aligned double-sided V-shaped ribs (DSVRs) over 30° ≤ θ ≤ 150°, 0.015 mm ≤ H r ≤ 0.035 mm, and 100 ≤ Re ≤ 900. Equal-branch V-ribs were positioned at corresponding locations on the opposing walls to examine acute-to-obtuse rib orientations. Among the investigated angles, θ = 30° generated the strongest secondary flow; outwardly directed streamwise vortices promoted cross-sectional fluid redistribution and thermal-boundary-layer disruption. At obtuse angles, the rib-guided flow converged toward the centerline and reversed the vortex rotation direction. Increasing H r strengthened the secondary flow and increased Nu , but also intensified blockage and frictional loss. The highest computed PEC at each investigated Re occurred at θ = 30°, with corresponding rib heights of H r = 0.035 mm at Re = 100 and 300, H r = 0.030 mm at Re = 500, and H r = 0.025 mm at Re = 700 and 900. The highest computed PEC among all investigated cases was 2.0273 at Re = 500, θ = 30°, and H r = 0.030 mm. Empirical correlations in a modified power-law form were developed for f and Nu at θ = 30° and 150°, with R 2 values of 0.9718–0.9964 and MAPE values of 2.11%–5.72%.
No takes yet. Share an insight, caveat, or question.
An et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: