Answers are grounded in this paper and cite their sources.
Among the various online monitoring methods for assessing the insulation condition of high-voltage cables, partial discharge (PD) detection is among the most widely applied. However, PD signals acquired in field environments are highly susceptible to noise interference. To address this issue, this paper proposes a PD signal denoising method that integrates the Rime Optimization Algorithm (RIME) with Variational Mode Decomposition (VMD) and Improved Wavelet Threshold (IWT) denoising. First, the RIME algorithm adaptively optimizes the number of modes K and the penalty factor α in VMD. The optimized VMD then decomposes the noisy PD signal into K intrinsic mode functions (IMFs), and the Composite Multiscale Fuzzy Dispersion Entropy (CMFDE) is introduced to characterize each IMF, thereby distinguishing effective signal components from noise components. Finally, IWT is applied to the effective components for secondary denoising to suppress residual noise and reconstruct the denoised PD signal. Simulation experiments and field-measured data demonstrate that the proposed method effectively removes noise interference in high-voltage cable PD signals and significantly improves the signal-to-noise ratio and reconstruction accuracy, enabling accurate online monitoring of high-voltage cable insulation condition.
No takes yet. Share an insight, caveat, or question.
Shang et al. (2026) studied this question.
Synapse has enriched 8 closely related papers on similar clinical questions. Consider them for comparative context: