Generators that are operated infrequently still require periodic maintenance, including warming-up operation to maintain operational readiness. Manual monitoring has limitations in recording operating time and electrical parameters. This study designs an Internet of Things (IoT)-based generator warming-up monitoring system using an ESP32 microcontroller, PZEM-004T sensor, DS1307 Real Time Clock (RTC), LCD, relay, buzzer, and Blynk application. The system measures voltage, current, power, frequency, and operating time, then displays and stores the data through Blynk. The overcurrent protection threshold is set to 3 A. Tests using six load variations produced voltage values of 228–232 V, current values of 0.04–2.13 A, and power values of 5–480.1 W. The reported average measurement errors were 0.8% for voltage, 4.4% for current, and 1.4% for power. During an overcurrent test at 3.30 A, the system detected the condition and disconnected the load supply through a relay within 1.05 seconds, accompanied by an alarm/notification. Data-storage tests showed that warming-up operating data could be recorded in Blynk in real time. The prototype therefore supports electrical-parameter monitoring and warming-up operation records, subject to Wi-Fi availability.