Answers are grounded in this paper and cite their sources.
Corona losses in high-voltage overhead lines depend on conductor voltage and geometry, surface condition, and atmospheric density, humidity, wind, and dust. This paper presents a physics-informed statistical model for estimating corona power loss per unit line length and integrating it over an operating period. The formulation combines a corrected inception-voltage criterion, a nonlinear voltage-dependent power term, and second-order interactions among normalized environmental variables. A 220 kV L–Bessopan (L–17) line is used as the study object. Under the stated baseline conditions, the relative air-density factor is 0.891. A previously calculated mean specific corona-loss power of 0.64 kW/km corresponds to 84.83 MWh over 184.1 km and 720 h. This is a computational illustration; validation requires synchronized electrical and meteorological measurements.
No takes yet. Share an insight, caveat, or question.
Tog'ayev Islom Bekpo'lat o'g'li (2026) studied this question.
Synapse has enriched 8 closely related papers on similar clinical questions. Consider them for comparative context: