Air-source heat pump drying (ASHPD) systems are recognised for their energy efficiency, utilising ambient air as a low-grade energy source for moisture removal in agricultural products. However, climatic conditions significantly affect their thermodynamic performance, influencing both energy consumption and coefficient of performance (COP). This study experimentally evaluated an ASHPD system with waste-heat recovery across ambient temperatures ranging from 20 deg C to -10 deg C, under open, semi-closed, and fully closed air-loop configurations. Results indicate that waste-heat recovery increased evaporator temperatures by 1.5 deg C in the semi-closed system and 9.4 deg C in the fully closed system, leading to heating capacity improvements of 6.7% and 30.7%, respectively. Consequently, COP increased by 4.2% and 16.9%. However, high condenser pressure in the fully closed configuration restricted operation to ambient temperatures above 10 deg C. As ambient temperature decreased, COP degradation was observed: 29.6% in the open system, 29.7% in the semi-closed system, and 19.9% in the fully closed system. These findings highlight the effectiveness of waste-heat recovery in improving ASHPD performance and mitigating efficiency losses under cold conditions, while emphasising the importance of selecting appropriate air-loop configurations based on climate.