The increasing penetration of inverter-based resources (IBRs) alters power grid dynamics, reducing inertia and damping. This work evaluates a supplementary Power Oscillation Damping (POD) controller for a power-controlled inverter, based on active power measurements at the Point of Common Coupling (PCC). The controller uses a washout and two-stage lead-lag structure, tuned for a dominant 7.7 Hz oscillatory mode identified by FFT analysis, and modulates the inverter active power reference in phase opposition to the oscillation. Performance is assessed through real-time electromagnetic transient (RTS-EMT) simulation in Typhoon HIL, using a 13.8 kV distribution feeder with a 6 MVA synchronous generator, for short-circuit ratios (SCR) of 3.10, 2.07, and 1.64 under a 10 % load step. The POD has a minor effect at SCR = 3.10, reduces the settling time from over 800 ms to approximately 350 ms at SCR = 2.07, and prevents the loss of stability observed without the controller at SCR = 1.64.