With the increasing share of converter-based generation units, these technologies must take over the grid stabilizing characteristics that synchronous generators inherently provide. Modern converters can emulate some of these characteristics through software updates by implementing a new control strategy known as grid-forming (GFM) control. Future grid connection codes will need to account for these capabilities and define the corresponding requirements. Within the hardware limitations of existing converters, GFM controls can provide several core capabilities, including virtual synchronous machine (VSM) behavior. In this study, a commercially available PV inverter is equipped with a VSM control strategy with defined inertia and damping constants comparable to those of conventional synchronous generators. The resulting behavior is compared with the characteristics of ideal current and voltage sources, as well as with the inverter’s original grid-following (GFL) control. Generic grid disturbances are applied to evaluate the dynamic response and experimentally assess the performance of the different control strategies. The measurements demonstrate that the GFM inverter fulfills the required core capabilities and exhibits clear voltage source behavior.