Answers are grounded in this paper and cite their sources.
To address the stability requirements of power systems with high renewable energy penetration, an optimal capacity configuration method for grid-forming energy storage systems (GFM-ESS) is proposed. The optimization model is first established with the objective of maximizing the average daily comprehensive profit of GFM-ESS, considering energy arbitrage revenue, ancillary service compensation, and investment, operation, and maintenance costs under typical operating scenarios. To simultaneously ensure system stability, nonlinear frequency stability and small-signal stability constraints are incorporated into the model. Data-driven approaches, namely hyperplane fitting and Bayesian linear regression, are employed to linearize the two types of stability constraints and construct a multi-type stability-constrained optimization framework. The proposed method is validated using a modified IEEE 39-bus system and a large-scale practical power system in northwestern China. The results suggest that the optimized GFM-ESS configuration helps reduce the risks of frequency instability and small-signal oscillations within the investigated test cases, while achieving coordinated improvements in both economic performance and operational efficiency. Furthermore, the case study on the practical large-scale power system confirms the applicability and effectiveness of the proposed method in renewable-rich power grids.
No takes yet. Share an insight, caveat, or question.
Li et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: