Answers are grounded in this paper and cite their sources.
Virtual synchronous generator (VSG) control can emulate inertia and damping in grid-forming converters, but active and reactive power remain coupled in low-voltage feeders with appreciable resistance. Model-based full-state feedback (FSF) can reduce this coupling, although its performance depends on the feeder parameters used by the controller. This study reproduces nominal FSF and evaluates its sensitivity to controller-side line-impedance errors. The proposed SMC-type dynamic compensation replaces static FSF compensation and is labeled SMC (sliding-mode control) in the comparisons. A reaching law driven by instantaneous power errors generates compensation rates via an estimated Jacobian. These rates are integrated to obtain angle and voltage corrections, without forming an integral sliding surface. A local reduced-order analysis gives a conditional ultimate-error bound under bounded residual disturbances, inactive limiters, and fast inner-loop tracking. Comparative simulations include power-command steps, grid-voltage and frequency disturbances, and a nine-point resistance–inductance estimation grid. SMC improves active-power settling at the sampled grid points. In one mismatch test with identical output slew-rate and amplitude limits, both controllers settle, but SMC settles faster and reduces the peak cross-channel deviation.
No takes yet. Share an insight, caveat, or question.
Chen et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: