Answers are grounded in this paper and cite their sources.
A scissor stairwell without the provision of a physical wall having suitable fire resisting rating for separating the scissor stair flights cannot be accepted by the authorities as a means of escape and safe egress provision for building occupants escaping from the building in the event of fire. However, as numerous high-rise buildings lack this provision, risk assessment is critical. Therefore, FDS was used to evaluate how stairwell configurations affect smoke dispersion and occupant tenability in these buildings. Compartment fires with various HRRs and floor locations were simulated in a 12-storey building under unventilated conditions to compare the simulation results of a straight-run stair in a stairwell with those of a stairwell for housing scissor stair flights in a single shaft without a physical wall separating the scissor stair flights. Results show that fire HRR and location dictate evacuation; first-floor fires prevent it, while sixth-floor fires leave lower levels smoke-free. The smaller volume of scissor stairwells generates higher temperatures and CO concentrations near the origin, but frictional resistance impedes vertical smoke propagation. Conversely, smoke reaches straight-run tops faster via the well-hole effect. Dimensionless visibility, temperature, and CO follow exponential profiles, with the scissor configuration delaying smoke filling by 15–20%.
No takes yet. Share an insight, caveat, or question.
Pešić et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: