Photovoltaic (PV) systems of several hundred kilowatts increasingly operate in low-voltage (LV) microgrids, yet field data on their power quality (PQ) and switching are scarce. We report Class A measurements (105 days in 12 sessions) at the feeder of a 500 kWp PV system in a university microgrid. Voltage indices remained within the EN 50160 benchmark limits (weekly 95th percentile total harmonic distortion, THD, ≤3.02%), and THD did not change when the inverters resumed generation. Current THD reached tens of percent at low output, but the total rated-current distortion stayed ≤0.67% (95th percentile). Passive identification from cloud-induced fluctuations gave a robust Thevenin resistance of 12.1 mΩ and a poorly constrained reactance of 8–17 mΩ, implying a PV-induced voltage rise of up to 3.5%. The inverters rode through dips to 0.59 p.u. while injecting balanced reactive current. Opening the PV feeder under load produced the largest deviations: instantaneous peaks of about 1.5 p.u. until the island voltage collapsed 65–85 ms after current interruption. An island frequency above 69 Hz and a residual voltage of up to 1.35 p.u. exceeded the analyser’s specified ranges and are indicative, but they inflated half-cycle root-mean-square values to 2.42 p.u., so waveform-based assessment is required.