This study presents a comprehensive experimental methodology for determining flammability limits of Hydrotreated Vegetable Oil (HVO) according to ASTM E681. Despite HVO's commercial adoption as "green diesel", essential safety parameters, including flammability limits, remain undocumented in current Safety Data Sheets. The experimental apparatus features a validated 20 L spherical glass vessel used for HVO testing, achieving a combined measurement uncertainty of ±2.19%. Theoretical calculations established operational ranges of temperature (130–180°C) and pressure (10–101 kPa) based on HVO vapor pressure characteristics and autoignition temperature (477 K). Validation demonstrates precise limit determination using visual flame propagation criteria, establishing the first standardized methodology for HVO flammability characterization. The results reveal a significant discrepancy: the lower flammability limit (LFL) of HVO deviates by up to 300% from predictions based on semi-empirical correlations by Zabetakis and Glassman, highlighting the inadequacy of conventional models for paraffinic biofuels and providing a foundation for comprehensive safety data generation.