In theory, cold plates under negative pressure systems should exhibit two-phase evaporation behavior. However, due to size and structural limitations, the working fluid in cold plates at high flow rates often exhibits single-phase heat absorption behavior simultaneously. The most important effect of single-phase heat absorption on cold plates is the resulting uneven temperature distribution on the heat source chip, which in turn reduces the chip’s lifespan.This study used eight types of microchannel cold plates as samples, with a heat source area of 30 × 30 mm2 and R1233zd as the working fluid. The validity of the cold plate evaporation rate was first assessed using the energy balance principle. Secondly, the correction coefficient of the Keyence clamp-on flowmeter used in this experiment with R1233zd was verified. Experimental results show that after correction, Sample 2 achieved the highest evaporation rate at 500 W, reaching 46.3%. The relatively low rate suggests that single-phase heat transfer dominated, resulting in an inlet-to-outlet temperature difference above 3°C for most of the cold plate. Furthermore, the evaporation rate decreases as the flow rate increases, but increases with higher power inputs. At a fixed power, the cold plate thermal resistance decreases as the flow rate increases.