Voltage recovery and transient rotor-angle stability are interconnected challenges in long-distance high-voltage transmission corridors. This study investigates an adaptive neuro-fuzzy inference system (ANFIS) controller for a 200 Mvar static var compensator (SVC) positioned at the midpoint of a nominal 250 km, 330 kV Ajaokuta–Benin corridor model. MATLAB/Simulink time-domain studies compared the uncompensated system with proportional-integral (PI), artificial neural network (ANN), and ANFIS-based SVC control under three-phase faults and loading levels from 80% to 120% of nominal. At Ajaokuta, the critical clearing time increased from 0.145 s without compensation to 0.195 s with PI-SVC, 0.225 s with ANN-SVC, and 0.265 s with ANFIS-SVC, corresponding to an 82.8% increase over the uncompensated case. At 120% loading, the ANFIS-SVC voltage recovery time was 1.3 s, compared with 3.2 s for PI-SVC and 5.5 s without compensation. In the nominal-load fault comparison, ANFIS-SVC reduced the reported voltage dip to 0.22 p.u., limited overshoot to 2.1%, and increased the damping ratio from 0.08 to 0.31. The simulation results indicate that neuro-fuzzy modulation of shunt reactive support can improve fault tolerance and post-fault voltage restoration in the investigated corridor model. The findings support further evaluation of adaptive SVC control using detailed network data and implementation-level testing.