Data centers constitute not only rapidly growing high-density loads but also potential flexible resources for distribution networks, enabled by suitable price signals and coordination mechanisms. However, under practical demand response rules with response thresholds and penalties for invalid responses, translating computational flexibility into valid and verifiable grid-side responses remains challenging. Here, we propose a bilevel framework that coordinates distribution network operations through dynamic electricity prices and schedules spatiotemporal workloads across multiple data centers. The framework explicitly incorporates the practical demand response mechanism implemented in Guangdong, China, and is solved by a lexicographic damped alternating algorithm with engineering stability. Simulations on a modified IEEE 32-bus system and a 60-bus practical system show that the proposed method decreases the cost of data centers, increases the accommodation of renewable energy, and improves valid response delivery. These results indicate that under threshold-based settlement, participation in the demand response is not necessarily beneficial unless flexibility can be delivered in a valid and verifiable form.