Answers are grounded in this paper and cite their sources.
High penetration of distributed energy resources and frequent extreme events challenge the operation of distribution networks. Numerous heterogeneous devices must be coordinated while accounting for their time-varying operating patterns and network constraints. This paper proposes an identification-modeling-regulation framework for distributed resource clusters. First, 768-dimensional temporal features extracted from eight seasonal day-type scenarios are reduced by principal component analysis and grouped into six clusters using K-means++. The held-out silhouette coefficient is 0.656 in a common standardized temporal feature space, compared with 0.591 for grouping by device type. Second, a two-level equivalent model uses clusters as control objects and 22 feeder blocks as injection units, yielding a maximum voltage deviation of 0.0151 p.u. and a loss underestimation of 4.09% at nominal load. Third, an event-driven regulation strategy formulates a linear program for each energized component and verifies the disaggregated device commands by detailed AC power flow. Case studies on a real 10 kV network with 214 modeled devices use synthetic annual operating profiles and planned wind and storage units. Under the modeled conditions, 71.57%, 83.31%, and 78.44% of total demand are served in the typhoon, heatwave, and thunderstorm scenarios, respectively.
No takes yet. Share an insight, caveat, or question.
Zhou et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: