Answers are grounded in this paper and cite their sources.
Peak load and the duration of elevated demand inform day-ahead storage preparation under electricity capacity pricing. Using 15 min loads from a Chinese provincial power system during 2022–2026, we compare an artificial intelligence (AI) model based on histogram gradient boosting (HGB) with linear models and weekly persistence on 447 common test dates. Monthly refitting reduces HGB peak-load mean absolute error (MAE) from 0.358 to 0.309 GW. Ridge regression records 0.269 GW under both protocols. With both models given lagged high-load durations, updated HGB and Ridge MAEs are 0.971 and 0.981 h, respectively, with no statistically significant paired difference. When underestimation carries five times the weight of overestimation, quantile training lowers HGB duration loss from 3.801 to 1.678 weighted h. The difference between HGB and linear quantile regression is not statistically significant. A separate station-day analysis finds that the negative association between regional mean load and external curtailment is not robust to load-shape controls. For storage preparation, these results support comparing peak and duration forecasts separately, using shared predictors and scoring each forecast under the error costs relevant to its intended use.
No takes yet. Share an insight, caveat, or question.
Zhao et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: