Plan form is often constrained by site and program, making orientation and proportion important early design choices. This study examined their combined effects on heating and cooling loads in Seoul office buildings (Köppen Dwa), where both loads are substantial. Rather than ranking plan forms, it quantified by load type how aspect ratio and orientation interact within each form. A full-factorial set of 240 EnergyPlus cases combining five plan forms, four aspect ratios, and twelve orientations was simulated with one thermal zone per floor. Variance decomposition showed that aspect ratio contributed most to cooling-load variation, whereas orientation contributed most to heating- and total-load variation. Plan form mainly shifted load levels without substantially changing the orientation–aspect-ratio response. Envelope area was associated with baseline loads, and the share of north- and south-facing façade area explained orientation-dependent variation. Annual total-load residual differences relative to the rectangular form were small and positive for all non-rectangular forms, consistent with a seasonal self-shading trade-off. Loads were lowest with north–south-facing long façades and aspect ratios of about 2–4, and highest at high aspect ratios with east–west-facing long façades. Long-façade orientation should therefore be assessed before aspect ratio is adjusted.