Radiant cooling systems are widely applied in building cooling owing to their superior thermal comfort and low energy consumption. The multi-radiant-surface configuration compensates for the insufficient cooling capacity of single-terminal systems. However, thermal comfort, condensation risk and energy consumption constrain each other during operation, and quantitative guidance for control strategy selection across building scenarios remains insufficient. Dynamic models of multi-radiant-surface cooling systems are established on TRNSYS for three building types in Jinan: residential buildings, office buildings and hospital wards. A total of 91 operating conditions are designed to compare three control strategies, and a comprehensive evaluation is conducted using the AHP-CRITIC-TOPSIS model. The results show that continuous PID control outperforms on-off control in thermal comfort, yet raises cooling-season energy consumption by 14.3–19.8%. The overall condensation risk remains controllable, while the constant-water-temperature variable-flow strategy exhibits a higher risk. For residential buildings and hospital wards, the optimal strategy is PID control with constant flow and variable water temperature, with relative closeness degrees of 0.699 and 0.858; for office buildings, the optimal strategy is PID control with constant water temperature and variable flow, with a relative closeness degree of 0.680. These findings provide quantitative references for control optimization of such systems.