Small-signal stability assessment of interconnected power systems requires a dynamic representation of neighboring areas whose detailed models may be unavailable. This study develops a measurement-driven Koopman dynamic equivalent using voltage-magnitude and phase-angle deviations at boundary buses as inputs and active- and reactive-power deviations on tie lines as outputs. A regularized regression in delay coordinates identifies the external-area input–output dynamics. Modal reduction prioritizes weakly damped modes with appreciable boundary-output salience and response energy. The reduced continuous-time realization is coupled to the detailed study-area model for eigenvalue analysis. In simulations of a 39-bus system, the dominant-mode frequency and damping-ratio errors were 0.11% and 1.41%, respectively, across cases with case-specific identification. A fixed equivalent evaluated on unseen load disturbances yielded errors of 0.141% and 1.865%, respectively. At a signal-to-noise ratio of 10 dB, the corresponding mean errors across 30 independent additive white Gaussian noise realizations were 0.978% and 7.351%. These results demonstrate the feasibility of boundary-measurement-based small-signal assessment in the simulated system and show that damping estimates are particularly sensitive to measurement noise.