Diesel generators that bridge scheduled grid outages in Iraqi households run mostly at low part load, where their electrical efficiency is about 12%. This study treats a 10 kW generator as a thermal energy converter and develops a forecast-aware controller for a household battery, using one year of measured load and PV data and a Baghdad-type outage timetable. Every hour the controller forms three load scenarios from a 24 h forecast and the out-of-fold quantiles of its error, and it solves a dynamic programme that contains the generator part-load fuel curve. It is compared with no storage, rule-based storage, grid pre-charge, a point-forecast controller and a perfect-foresight bound. A 5 kWh battery reduces diesel use from about 2290 to 212 L/yr (91% against no storage, 82% against rule-based storage), and the efficiency of the remaining generator operation rises from about 12% to 25%. The scenario controller uses 2.3–3.7% less diesel than the point-forecast controller and realises 76–86% of the achievable gain. Neural-network and gradient-boosting forecasters did not reduce fuel use further; planning around the forecast error did. Including grid pre-charging, 78–83% of the fuel energy of the no-storage case is saved. The benefit of choosing the operating point depends on the assumed low-load fuel curve.