Answers are grounded in this paper and cite their sources.
Variable refrigerant flow (VRF) systems are widely used for multi-room climate control, where multiple indoor units share a common refrigeration circuit. Conventional rule-based and feedback control strategies provide reliable operation, but the inherent coupling among shared compressor capacity, refrigerant distribution, and room-side cooling demands makes energy-efficient control challenging. A key challenge is to coordinate coupled actuators, including compressor operation and room-side devices, which jointly determine cooling capacity allocation across the system. In this paper, the authors propose an expert-rule-constrained residual cyan!22reinforcement learning (RL) framework for multi-room VRF systems. The proposed framework retains an expert-rule controller and integrates reinforcement learning to learn bounded residual adjustments, improving energy efficiency while preserving coordinated system operation. The framework is implemented with the Truncated Quantile Critics (TQC) algorithm and evaluated in a four-room VRF simulation environment. Under representative evaluation conditions, the TQC-based residual reinforcement learning method reduces cumulative energy consumption by 7.7% compared with the expert-rule controller without learned residuals. The proposed approach maintains high room-time comfort compliance during late-stage operation, demonstrating the potential of residual RL for improving energy efficiency in complex refrigeration systems while retaining existing control knowledge.
No takes yet. Share an insight, caveat, or question.
Huang et al. (2026) studied this question.