Building energy model (BEM) simplification can reduce modelling effort, but its effect on energy predictions and retrofit rankings remains uncertain. This study compared three independently calibrated EnergyPlus models of one high-rise office building in Ottawa, Canada, to examine annual, monthly and peak energy predictions and energy-based retrofit rankings. Geometry, thermal zoning and HVAC representation were progressively simplified, and 576 combinations of five energy conservation measure parameters were evaluated at each resolution. For the baseline configurations, annual deviations from the detailed model were 1.2 %, 2.3 % and 1.7 % at medium resolution and −2.6 %, 1.1 % and 4.1 % at low resolution for heating, cooling and non-HVAC electricity, respectively. Simulated peak cooling differed by −9.5 % and +12.2 % at medium and low resolutions. These are model-to-model differences; peak accuracy was not validated against measured hourly demand. Heating and cooling rankings remained strongly similar (Spearman’s ρ ≥ 0.997). The only changed minimum-heating selection differed by 0.011 % in detailed-model energy use, indicating a near-tie. For this case and design space, annual-energy screening priorities were largely preserved despite greater differences in hourly and peak outputs. Independent calibration limits attribution of these differences to resolution alone.
No takes yet. Share an insight, caveat, or question.
Saleem et al. (2026) studied this question.