Answers are grounded in this paper and cite their sources.
This article presents a reference design for a hybrid power plant consisting of a wind farm, solar photovoltaics (PV) farm, and battery energy storage system. The power plant is designed for an onshore site in western Denmark and for a limited grid connection capacity of 300 MW. The wind farm is made of 65 NLR 5 MW reference turbines, for a total capacity of 325 MW, placed in a grid layout. The solar PV farm consists of 59 modular solar PV systems with a total capacity of 400 MWp and an AC/DC ratio of 1. The storage system has a power capacity of 150 MW and an energy capacity of 300 MWh, divided into 60 lithium-ion battery units. We present an example simulation of the design and associated performance metrics. The novelty of this dataset resides in the high level of detail in the specification of each of the components, thereby enabling advanced simulation studies and supporting research and development efforts for hybrid power plants.
No takes yet. Share an insight, caveat, or question.
Iori et al. (2026) studied this question.