Answers are grounded in this paper and cite their sources.
Battery thermal loads in peak-shaving energy storage systems vary rapidly with power, creating a trade-off between thermal safety and auxiliary energy consumption. This study proposes an air−liquid hybrid thermal management architecture with a shared variable-capacity vapor-compression chiller and develops a pareto-optimized hybrid supervisory control (POHSC) for system-level energy reduction. The chiller supplies both an air coil and liquid cold plates, enabling air-side, liquid-side, or simultaneous cooling without duplicating refrigeration hardware. A five-zone lumped thermal model, identified from three-dimensional conjugate heat-transfer simulations, retains the principal spatial temperature distribution while enabling efficient day-scale control analysis. Offline Pareto optimization determines switching boundaries, and the online controller assigns air cooling to low-to-moderate thermal loads while reserving liquid cooling for short high-load periods. For a representative high-cooling-load day in Xi’an, POHSC limits the maximum zone-average temperature and maximum interzone temperature difference to 30.023 °C and 3.641 K, respectively. Daily auxiliary energy consumption is 18.014 kWh, 20.87% lower than pure liquid cooling. Although the liquid branch operates for only 1.38 h, it removes 61.9% of cumulative heat. The results demonstrate that energy savings arise from hierarchical matching of cooling intensity to dynamic thermal demand under a shared cooling source.
No takes yet. Share an insight, caveat, or question.
Jiang et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: