This study analyzes the cybersecurity of a Wide Area Monitoring, Protection, and Control (WAMPAC) system deployed for the secure interconnection of the electric power systems of Brazil, Paraguay, and Argentina. The research examines the system architecture, the security exposure of the IEC 60870-5-104, IEC 61850, and IEEE C37.118 protocols, the implemented cybersecurity controls, the resilience limitations of the MPLS/TP transport network, and the economic impact associated with service unavailability. The results identify relevant weaknesses arising from the lack of native encryption, authentication, and integrity mechanisms in the analyzed protocols. To mitigate these risks, the implemented protection scheme includes next- generation firewalls, DoS protection policies, intrusion prevention and detection systems (IPS/IDS), application control, OT monitoring, SIEM integration, centralized security updates, automatic backup, and controlled remote access through a jump server. The study also shows that the current MPLS/TP design presents availability limitations and that Pseudowire Redundancy (PWR), complemented by Multi-Segment Pseudowire (MS-PW), is a viable option for improving recovery times and operational continuity. The economic analysis shows that direct cybersecurity investment represents a small fraction of the total project cost, while potential losses associated with the Cost of Energy Not Supplied (CENS) can far exceed that investment.