Transformers are essential power system equipment and continuously generate no‐load losses when energised. So, calculating the no‐load losses caused by the transformer must be performed at the design stage. No‐load current in transformers also determines the efficiency of the transformer. No‐load current is divided into iron current and magnetisation current. Depending on the induction of the transformer, the effect of the no‐load current components also changes. Therefore, this paper discusses the no‐load loss (P s) and reactive power (Q s) curves of the core in terms of induction and frequency dependence for different materials. P s and Q s have the same value at certain points, but especially as the material gets closer to the saturation region, the reactive power increases rapidly and becomes higher than P s. Analyses on a real transformer were performed in Ansys Maxwell and compared with test results. It was concluded that the no‐load current does not depend only on the core loss, and the effect of reactive power should be taken into consideration when making evaluations.