High temperature heat pumps (HTHPs) are expected to highly contribute to industrial decarbonation. As current state-of-the-art technologies do not cover sufficiently wide temperature ranges and have limited exergy efficiency, a novel CO 2 heat pump, where compression and expansion transformations are achieved with a hydraulic piston, was developed to minimize exergy losses. This paper studies a novel architecture that is designed for exergy loss minimization. Theoretically, the hydro-CO 2 heat pump enables isochoric, isentropic, quasi-isothermal transformations and novel thermodynamic cycles. To describe this novel cycle, a numerical model details the performance in ideal conditions and shows maximal COPs of 1.82 at the heat source and 2.76 at the heat sink with a temperature lift of 187 K. To evaluate exergy losses on a real system, a laboratory-scale prototype was developed. Experimental results show that standard compressions achieved with the hydro-CO 2 system are far from the isentropic isoline, with an isentropic performance of 15.6%, mainly because of heat losses. Those heat losses are estimated with an additional numerical model, which is validated with the experimental data. The final simulations show that upscaling the prototype towards greater dimensions and reducing the compression time by a factor 10 allows to reach an isentropic performance of 87.3% without improving insulation solutions. The provided conclusions validate the hydro-CO 2 heat pump potential to provide better compression solutions.