Answers are grounded in this paper and cite their sources.
Wind-induced conductor reactions contribute to the loading of overhead transmission-line supports, yet their dependence on span length, wind speed, and support arrangement requires further assessment. This study investigates the along-wind reaction at the central support of two equal conductor spans using aeroelastic wind-tunnel tests, Davenport-based analysis, and finite element simulations. The measured reaction standard deviation was 0.028 N, compared with an analytical prediction of 0.0294 N. At prototype scale, the analytical standard deviation was 0.3944 kN, compared with 0.39 kN from simulation. Neglecting resonance underestimated the fluctuating peak increments by 18.4% and 8.7% at model and prototype scales, respectively, while reducing the conductor-side design contributions by 3.6% and 1.3% with a separation coefficient of 0.75. The conductor-only peak-to-mean reaction factor generally decreased with increasing span length and varied non-monotonically between 1.45 and 1.54 over wind speeds of 20–50 m/s. The three idealized central-support arrangements (hinged, I-type, and V-type) yielded similar conductor-only factors (1.44–1.45) and reduced design combination factors (1.33–1.34) for a 400-m span at 30 m/s. These findings quantify the contributions of resonance and the effects of key parameters on conductor-induced support reactions under the investigated conditions.
No takes yet. Share an insight, caveat, or question.
Tang et al. (2026) studied this question.