Answers are grounded in this paper and cite their sources.
The Three-Phase Two-Wire (TPTW) earth-return system is a cost-effective topology for rural electrification, but its inherent spatial asymmetry and high R/X ratios severely restrict photovoltaic (PV) Hosting Capacity. Under reverse power flows, these weak grids experience critical overvoltages and normative phase unbalance violations. This paper proposes optimizing decentralized Volt-Var Control (VVC) within standard smart inverters to act as a communication-free Non-Wires Alternative (NWA) for a 50 km TPTW feeder. Using a mathematically rigorous model based on Carson’s equations and 24-hour Quasi-Static Time Series (QSTS) simulations, the daily evolution of the voltage profile and Voltage Unbalance Factor (VUF) is evaluated across different conductor gauges. Results demonstrate that a strict Grid Search parameter tuning—characterized by a narrowed deadband and high reactive absorption gain— effectively mitigates daytime PV overvoltages and clamps the VUF well below the 2.0% limit. Furthermore, the QSTS analysis transparently maps the physical boundaries of this strategy, revealing the structural load capacity collapse of highly resistive cables (4 AWG) during nighttime peaks. Ultimately, this autonomous VVC parameterization significantly expands renewable hosting capacity while directly avoiding the massive capital expenditures (CAPEX) associated with physical grid reconductoring.
No takes yet. Share an insight, caveat, or question.
Rabelo et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: