Fast and reliable test methods are required when developing intumescent coatings. In this work, the “CoaST‐Fire,” a medium‐scale setup, was evaluated using 52 intumescent coating samples. The samples consisted of 11 commercial coatings from six manufacturers. The effect of coating thickness and steel section factor was investigated for some of the coatings. The char thickness, weight loss, and effective thermal conductivity were determined. The results were used to make performance predictions that were compared to the certified fire resistance time, determined according to EN 13381‐8 and/or BS476‐20/21. The constant effective thermal conductivity of the coating samples was shown to be inversely proportional to the expansion factor (final char thickness to initial coating thickness). Generally, the expansion factor decreased with an increase in coating thickness or decrease in section factor, suggesting that a higher heating rate of the coating results in a higher expansion. Coating thickness and section factor had no consistent effect on weight loss. For coatings with a high expansion factor, the predictions did not agree well with the certified fire resistance because of the flat steel panels that were used, which do not capture problems that arise due to the curvature of the samples used in the full‐scale fire resistance tests. For samples with an expansion factor of less than 30, the predictions were within 30% of the certified fire resistance time. This may sound high but given the difficulty in scaling down fire resistance tests of intumescent coating, it can provide an early quantitative indication of the coating performance when developing new coating formulations.
No takes yet. Share an insight, caveat, or question.
Olsson et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: