This study evaluates the energy and environmental performance of heating, ventilation, and air-conditioning systems in two standalone commercial building models in Makkah, Saudi Arabia: a 700 m 2 supermarket served by two packaged rooftop air systems and a 300 m 2 office equipped with a variable refrigerant flow system. The supermarket results should be interpreted as representing HVAC-related and general building electricity demand only because dedicated commercial refrigeration systems were not modeled. The buildings were simulated using EnergyPlus under two scenarios: a grid-only baseline and a solar-integrated configuration incorporating grid-connected photovoltaic systems without battery storage. A Typical Meteorological Year weather file was used to represent a typical annual simulation cycle. Operational CO 2 emissions were calculated from gross grid electricity imports using an emission factor of 0.568 kg CO 2 /kWh, while exported photovoltaic electricity was tracked separately and was not assigned an avoided-emission credit. The supermarket consumed 221,279.34 kWh annually, including 105,725.20 kWh for cooling, whereas the office consumed 39,005.87 kWh, including 17,401.14 kWh for cooling. The photovoltaic systems generated 245,639.59 kWh for the supermarket and 54,847.54 kWh for the office. Despite photovoltaic generation exceeding annual electricity demand in both buildings, temporal mismatches between generation and demand resulted in residual grid imports of 109,214.76 and 11,271.97 kWh, respectively. Consequently, annual operational CO 2 emissions decreased from 125,686.69 to 62,033.99 kg CO 2 for the supermarket and from 22,155.34 to 6402.48 kg CO 2 for the office, corresponding to reductions of 50.64% and 71.10%. The energy use intensities were 316.11 and 130.02 kWh/m 2 /year, while cooling represented 47.78% and 44.61% of total electricity demand. Descriptive regression analysis was used only to summarize relationships within the simulation-generated dataset and was not interpreted as independent causal validation. The findings demonstrate that annual net-positive photovoltaic generation does not imply continuous grid independence and highlight the importance of evaluating gross imports, exports, and load-generation matching when assessing the decarbonization potential of commercial buildings in hot climates.
No takes yet. Share an insight, caveat, or question.
AlKhatib et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: